Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Discrete input number | 32 |
| Product or component type | low voltage dc discrete input modules |
| Range of product | Modicon Quantum automation platform |
| Complementary | |
| Maximum leakage current | 200 mA at Us = 5.5 V and Uin = 4 V |
| Module format | standard |
| Protection type | input protection |
| Absolute maximum input | 5.5 V continuous, 15 V during 1.3 ms decaying pulse |
| Input impedance | 7500 Ohm |
| Local signalling | 32 LEDs (green) for input status, 1 LED (red) for external fault detected (F), 1 LED (green) for bus communication is present (Active) |
| Addressing requirement | 2 input words |
| Bus current requirement | 170 mA |
| Voltage state 1 guaranteed | 0.8 V DC |
| Voltage state 0 guaranteed | >= 4 V DC at 5.5 V supply voltage |
| Net weight | 0.45 kg |
| Isolation between group | 500 Vrms for 1 minute |
| Input voltage limits | 4.5...5.5 V |
| Current state 1 guaranteed | 4 mA |
| Marking | CE |
| Response time | <= 500 µs from state 1 to state 0, <= 250 µs from state 0 to state 1 |
| Isolation between group and bus | 1780 Vrms for 1 minute |
| Discrete input voltage | 5 V TTL DC |
| Group of channels | 4 |
| Power dissipation | 5 W |
| Logic input | negative (source) |
| Environment | |
| Operating altitude | <= 5000 m |
| Resistance to electrostatic discharge | 8 kV on air conforming to IEC 801-2, 4 kV contact conforming to IEC 801-2 |
| Relative humidity | 95-95 % without condensation |
| Ambient air temperature for storage | -40-85 °C |
| Standards | UL 508, CSA C22.2 No 142 |
| Resistance to electromagnetic fields | 10 V/m 80-2000 MHz conforming to IEC 801-3 |
| Ambient air temperature for operation | 0-60 °C |
| Product certifications | cUL, FM Class 1 Division 2, GOST |