Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Protective treatment | TC |
| Discrete input number | 10 conforming to IEC 1131-2 Type 2 |
| Discrete input logic | positive |
| Discrete output number | 8 |
| Discrete output voltage | 120...132 V DC |
| Product or component type | discrete triac I/O base AC |
| Discrete input voltage | 120 V AC |
| Discrete output logic | positive |
| Range of product | Modicon Momentum automation platform |
| Group of channels | 1 group of 8 outputs, 1 group of 10 inputs |
| Discrete output type | triac |
| Complementary | |
| [Us] rated supply voltage | 120 V AC |
| Discrete output current | 30 mA...0.5 A per point, 4 A per module, 2 A per group |
| Depth | 47.5 mm |
| Width | 125 mm |
| Protection type | internal 2 x 2.5 A slow-blow fuses |
| Input resistance | 4 kOhm |
| Voltage state 1 guaranteed | > 74 V |
| Maximum leakage current | 1.3 mA at 120 V (output circuit) |
| Voltage state 0 guaranteed | < 20 V |
| Net weight | 0.22 kg |
| Response time | 1/2 x 1/f from state 1 to state 0 on output, 1/2 x 1/f from state 1 to state 0 on input, 1/2 x 1/f from state 0 to state 1 on output, 1/2 x 1/f from state 0 to state 1 on input |
| Input voltage limits | 74...132 V |
| Current state 0 guaranteed | <= 2.6 mA |
| Marking | CE |
| Current state 1 guaranteed | >= 6 mA |
| Current consumption | 160 mA at 120 V AC |
| Isolation between channels and bus | 1780 V AC |
| Maximum voltage drop | <1.5 V 0.5 A at state 1 output circuit |
| Terminals description PLC n°1 | (2)IN_DIS#2, TB, (1)IN_DIS#1, (7)IN_DIS#7, (6)IN_DIS#6, (N)PW, (L1)PW, (3)IN_DIS#3, (10)IN_DIS#10, (4)IN_DIS#4, (9)IN_DIS#9, (5)IN_DIS#5, (8)IN_DIS#8 |
| Terminals description PLC n°2 | TB_1, (5)OUT_DIS#5, (4)OUT_DIS#4, (1)OUT_DIS#1, (7)OUT_DIS#7, (8)OUT_DIS#8, (1L1)PW, (2)OUT_DIS#2, (1N)PW, (6)OUT_DIS#6, (3)OUT_DIS#3 |
| Operating rate | 3000 cyc/h 0.5 A inductive |
| Height | 141.5 mm |
| Power dissipation | 6 W, <= 8 W |
| Network frequency | 47...63 Hz |
| Environment | |
| Operating altitude | <= 5000 m |
| Resistance to electrostatic discharge | 8 kV on air conforming to IEC 801-2, 4 kV contact conforming to IEC 801-2 |
| Relative humidity | 95-95 % without condensation |
| Ambient air temperature for storage | -40-85 °C |
| Resistance to electromagnetic fields | 10 V/m 80...1000 MHz conforming to IEC 801-3 |
| Ambient air temperature for operation | 0-60 °C |
| Product certifications | CSA, UL |