Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| [In] rated current | 25 A at 40 °C |
| Standards | EN/IEC 60947-2 |
| Breaking capacity code | H |
| Product or component type | miniature circuit-breaker |
| Product name | Acti9 NG125 |
| Utilisation category | category A conforming to IEC 60947-2 |
| Poles description | 1P |
| Range of product | NG125 |
| Curve code | C |
| Range | Acti9 |
| Breaking capacity | 36 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2, 36 kA Icu at 12 V DC conforming to EN/IEC 60947-2, 70 kA Icu at 110...130 V AC 50/60 Hz conforming to EN/IEC 60947-2, 36 kA Icu at 125 V DC conforming to EN/IEC 60947-2, 25 kA Icu at <= 144 V DC conforming to EN/IEC 60947-2, 9 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Device short name | NG125H |
| Network type | AC, DC |
| Trip unit technology | thermal-magnetic |
| Number of protected poles | 1 |
| Suitability for isolation | yes conforming to IEC 60947-2 |
| Device application | distribution |
| Complementary | |
| Network frequency | 50/60 Hz |
| Total power losses | 2.7 W |
| Contact position indicator | yes |
| Mounting support | 35 mm symmetrical DIN rail |
| Local signalling | trip indicator, ON/OFF indication |
| Mounting position | vertical |
| Width | 27 mm |
| Depth | 81 mm |
| [Ue] rated operational voltage | 380...415 V AC 50/60 Hz, 125 V DC, <= 144 V DC, 12 V DC, 220...240 V AC 50/60 Hz, 110...130 V AC 50/60 Hz |
| Wire stripping length | 20 mm |
| Control type | toggle, manual tripping test |
| Mounting mode | clip-on |
| Power losses per pole | 2.7 W |
| Mechanical durability | 20000 cycles |
| Connection pitch | 27 mm between devices |
| Tightening torque | 3.5-3.5 N.m |
| 9 mm pitches | 3 |
| Magnetic tripping limit | 8 x In +/- 20 % |
| Net weight | 0.24 kg |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Market segment | small commercial, small buildings |
| Locking options description | integrated padlocking |
| [Ics] rated service breaking capacity | 52.5 kA 75 % conforming to EN/IEC 60947-2 - 110...130 V AC 50/60 Hz, 27 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz, 6.75 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz, 36 kA 100 % conforming to EN/IEC 60947-2 - 60 V DC, 36 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC |
| Height | 103 mm |
| Earth-leakage protection | without |
| Comb busbar and distribution block compatibility | YES |
| Connections - terminals | tunnel type terminals1.5-50 mm² rigid, tunnel type terminals1-35 mm² flexible |
| Electrical durability | 10000 cycles |
| Compatibility code | NG125 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
| Provision for padlocking | padlockable |
| Environment | |
| IK degree of protection | IK05 conforming to EN/IEC 62262 |
| Ambient air temperature for operation | -30-70 °C |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60947-2 |
| Overvoltage category | IV |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Ambient air temperature for storage | -40-70 °C |
| Relative humidity | 95-95 % at 55-55 °C |
| Contractual warranty | |
| Warranty | 18 |