| Attribute name | Attribute value |
|---|---|
| Main | |
| Device short name | Vigi C120 |
| Poles description | 3P |
| Earth-leakage protection time delay | instantaneous |
| Product or component type | add-on residual current devices |
| Earth-leakage sensitivity | 30 mA |
| Earth-leakage protection class | type A |
| Network type | AC |
| Range of product | C120 |
| [In] rated current | 125 A |
| Complementary | |
| [Ue] rated operational voltage | 400...415 V AC 50/60 Hz |
| Product compatibility | single terminal |
| Tightening torque | 3.5-3.5 N.m |
| Depth | 73 mm |
| Market segment | small commercial, residential |
| Width | 171 mm |
| Colour | white |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Compatibility code | Vigi C120 |
| Mechanical durability | 20000 cycles |
| Mounting mode | clip-on |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60947-1 |
| Residual current tripping technology | voltage independent |
| Electrical connection to mcb | by screws |
| Wire stripping length | 15 mm |
| Net weight | 0.5 kg |
| 9 mm pitches | 10 |
| Device location in system | outgoer |
| Mounting support | 35 mm symmetrical DIN rail |
| Connections - terminals | tunnel type terminals 1-50 mm² rigid, tunnel type terminals 1-35 mm² flexible |
| Height | 95 mm |
| Network frequency | 50/60 Hz |
| Environment | |
| Ambient air temperature for storage | -40-60 °C |
| Pollution degree | 3 conforming to IEC 60947-2 |
| IP degree of protection | IP20 |
| Standards | IEC/EN 61009-2-1, EN 61009 |
| Ambient air temperature for operation | -25-60 °C |