| Attribute name | Attribute value |
|---|---|
| Main | |
| Rated power in W | 25 W |
| Input voltage | 100...240 V AC phase to phase, 100...240 V AC single phase |
| Output voltage | 12 V DC |
| Range of product | Modicon Power Supply |
| Enclosure material | plastic |
| Power supply output current | 2.1 A |
| Power supply type | regulated switch mode |
| Product or component type | power supply |
| Complementary | |
| Power factor | 0.38 at 230 V AC, 0.48 at 115 V AC |
| Inrush current | 50 A at 230 V, 25 A at 115 V |
| Efficiency | 85 % at 230 V AC, 85 % at 115 V AC |
| Load capacitance | 3000 µF |
| Power dissipation in W | 4.6 W |
| Meantime between failure [MTBF] | 1000000 h at 55 °C, 80 % load, 2500000 h at 25 °C, full load |
| Input protection type | external protection (recommended) 4 A Curve C, external protection (recommended) 4 A Curve B, external protection (recommended) 20 A Curve C, external protection (recommended) 20 A Curve B, integrated fuse (not interchangeable) 3.15 A |
| Network frequency limits | 50-60 Hz |
| Connections - terminals | screw connection: 0.5...1 mm², (AWG 20...AWG 18) with wire end ferrule for input/output, screw connection: 0.5...1.5 mm², (AWG 20...AWG 16) without wire end ferrule for input/output |
| Earthing system | IT, TT, TN |
| Input voltage limits | 90...264 V AC |
| Status LED | 1 LED (green) output voltage |
| Residual ripple | < 100 mV |
| Height | 91 mm |
| Depth | 55.6 mm |
| Overvoltage category | II |
| Width | 36 mm |
| Line and load regulation | < 1 % at 0 to 100 % load, < 0.5 % at in line |
| Response time | < 2 s |
| Mounting support | panel mounting, double-profile DIN rail, top hat type TH35-7.5 rail conforming to IEC 60715, top hat type TH35-15 rail conforming to IEC 60715 |
| Output voltage limits | 12...15 V |
| Service life | 10 year(s) |
| Output protection type | against overvoltage, protection technology: manual reset, against over temperature, protection technology: manual reset, against overload and short-circuits, protection technology: automatic reset |
| Maximum leakage current | 0.25 mA 240 V AC |
| Net weight | 0.170 kg |
| Supply | SELV conforming to IEC 60364-4-41, SELV conforming to IEC 60204-1, SELV conforming to IEC 60950-1 |
| Current consumption | < 0.6 A 230 V AC, < 0.8 A 115 V AC |
| Dielectric strength | 3000 V AC input/output |
| Holding time | > 60 ms 230 V AC, > 20 ms 115 V AC |
| Output coupling | serial |
| Environment | |
| IP degree of protection | IP20 |
| Electromagnetic compatibility | conforming to EN 55016-2-1, conforming to EN 55016-1-2, limits for harmonic current emissions conforming to IEC 61000-3-2, disturbing field emission conforming to EN 55016-2-3, immunity to voltage dips - test level: 30 % (25 cycles) conforming to IEC 61000-4-11, immunity to voltage dips - test level: 60 % (10 cycles) conforming to IEC 61000-4-11, immunity to voltage dips - test level: 100 % (1 cycle) conforming to IEC 61000-4-11, immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8, immunity to conducted disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6, surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5, surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5, immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4, electromagnetic field immunity test - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3, electromagnetic field immunity test - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3, electromagnetic field immunity test - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3, immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2, immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2 |
| Pollution degree | 2 |
| Product certifications | NEC: class 2, KC, EAC, CB Scheme, RCM, cUL recognized, cUL listed, CE |
| Ambient air temperature for operation | 55-70 °C with current derating of 2.67 % per °C mounting position A < 2000 m, -25-55 °C without current derating mounting position A < 2000 m |
| Electromagnetic emission | radiated emissions conforming to IEC 61000-6-4, conducted emissions conforming to IEC 61000-6-3 |
| Electrical shock protection class | class II without PE connection |
| Operating altitude | 2000 m...5000 m overvoltage category II, < 2000 m overvoltage category III |
| Vibration resistance | 10 m/s² (f= 9-200 Hz) conforming to IEC 60721-3-3, 3 mm (f= 2-9 Hz) conforming to IEC 60721-3-3 |
| Shock resistance | 150 m/s² for 11 ms |
| Standards | EN/IEC 62368-1, CSA C22.2 No 61010-2-201, CSA C22.2 No 61010-1, CSA C22.2 No 62368-1, UL 61010-2-201, UL 61010-1, UL 62368-1, EN 61000-3-3, IEC 61000-3-2, IEC 61000-6-4, IEC 61000-6-3, IEC 61000-6-2, IEC 61000-6-1, EN/IEC 61204-3, EN 61010-2-201, EN/IEC 61010-1, IEC 62368-1 |
| Variant option | modular |