| Attribute name | Attribute value |
|---|---|
| Main | |
| Product compatibility | all backplane |
| Supply circuit type | DC |
| Secondary power | 40 W 24 V DC at -25-60 °C I/O module power supply and processor if 3.3 V not loaded, 18 W 3.3 V DC at -25-60 °C I/O module logic power supply |
| Function available | uptime duration, temperature sensing, remaining lifetime, redundancy test, redundancy information |
| Product or component type | power supply module |
| Range of product | Modicon X80 |
| Primary voltage | 125 V |
| Complementary | |
| Protection type | short-circuit protection for secondary circuit, overvoltage protection for secondary circuit, overload protection for secondary circuit, internal fuse not accessible for primary circuit |
| Inrush current | 60 A 125 V |
| Electrical connection | 1 connector 5 pin(s)line supply, protective earth, 1 connector 2 pin(s)alarm relay |
| Maximum power dissipation in W | 8.5 W |
| Control type | RESET push-button cold restart |
| Net weight | 0.64 kg |
| Insulation resistance | >= 100 MOhm primary/secondary, >= 100 MOhm primary/ground |
| Current at secondary voltage | 5 A 3.3 V DC I/O module power supply and processor, 1.67 A 24 V DC I/O module logic power supply |
| Input current | 600 A 125 V |
| I²t on activation | 2.5 A².s 125 V |
| Status LED | 1 LED (green) power supply status, 1 LED (green) redundancy OK, 1 LED (green) presence of voltages (OK) |
| It on activation | 0.09 A.s 125 V |
| Primary voltage limit | 100...150 V |
| MTBF reliability | 791000 H |
| Environment | |
| Dielectric strength | 1500 V primary/ground, 2300 V primary/secondary sensor power supply, 1500 V primary/secondary I/O module power supply and processor, 1500 V primary/secondary I/O module logic power supply |
| IP degree of protection | IP20 |
| Protective treatment | conformal coating |
| Operating altitude | 2000...5000 m with derating factor, 0...2000 m |
| Relative humidity | 5-95 % at 55-55 °C without condensation |
| Ambient air temperature for storage | -40-85 °C |
| Directives | 2014/34/EU - ATEX directive, 2006/42/EC - machinery, 2014/30/EU - electromagnetic compatibility |
| Vibration resistance | 3 gn |
| Environmental characteristic | fungal spore resistant class 3B2 conforming to IEC 60721-3-3, mold growth resistant class 3B2 conforming to IEC 60721-3-3, salt resistant level 2 conforming to IEC 68252, sand resistant class 3S4 conforming to IEC 60721-3-3, dust resistant class 3S4 conforming to IEC 60721-3-3, gas resistant class 3C4 conforming to IEC 60721-3-3, gas resistant class Gx conforming to ISA S71.04, hazardous location class I division 2 |
| Shock resistance | 15 gn |
| Product certifications | TÜV, IECEx zone 2/22, ATEX zone 2/22, Merchant Navy, EAC, RCM, CSA, UL, CE |
| Standards | EN/IEC 60079-0, EN/IEC 61850-3, location G, EN/IEC 61000-6-5, interface type 1 and type 2, IACS E10, CSA C22.2 No 61010-2-201, UL 61010-2-201, EN/IEC 61010-2-201, EN/IEC 61131-2 |
| Immunity to microbreaks | 1 ms |