Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Range | PowerLogic |
| Product or component type | voltage module |
| Complementary | |
| Noise level | 75-75 dB |
| Location of connection | bottom |
| Sag correction response | 3 ms |
| Poles description | 3P + N, 3P |
| Sag correction capability | For 3 phases 40-40 % for 30 s, accuracy +/- 1 % |
| Efficiency | non-linear load at at nominal power load factor (97.4 %), linear load at at nominal power load factor ,PF 1 (98.1 %), linear load at at nominal power load factor ,PF 0.8 (97.7 %), at global efficiency load factor (98 %) |
| Output voltage accuracy | +/- 1 % typical |
| Enclosure mounting | floor-standing |
| Mean time to repair | 2 h |
| Type of cooling | forced cooling |
| Network frequency | 50/60 Hz +/- 10 % |
| Function available | secondary function |
| Electromagnetic compatibility | emission standard for industrial environments conforming to IEC 61000-6-4, immunity for industrial environments conforming to IEC 61000-6-2, voltage dips and interruptions immunity test conforming to IEC 61000-4-34 |
| Ride-through time | 40 ms |
| Material | hot-rolled steel, cold-rolled steel |
| [THDU] total harmonic distorsion | 10-10 % (limit), 8-10 % (short time): output voltage regulated at +/- 3 %, 5-8 % (maximum): output voltage regulated at +/- 1 %, 0-5 % (nominal) |
| Surface finish | polyester powder |
| Network rated voltage | 400-400 V AC |
| Admitted output load | inverter overload 150 %, 1 s, inverter overload 110 %, 30 s, up to 100% in unbalance, up to 100% in variation |
| Continuous regulation range | -20-20 % |
| Overload withstand | 30 In, if overload is exceeded equipment integrity is not guaranteed, 200 ms, 30 In, 200 ms, 5 In, 10 s, 2 In, 60 s |
| Reactive power rating | 900 kVA |
| Accessibility for operation | front |
| Environment | |
| IP degree of protection | IP20 |
| Depth | 750 mm |
| Overvoltage category | III |
| Width | 1214 mm |
| Colour | light grey (RAL 7035) |
| Operating altitude | <= 1000 m without derating |
| Relative humidity | 0-95 % non-condensing |
| Ambient air temperature for storage | -15-45 °C |
| Net weight | 1250 kg |
| Pollution degree | 2 |
| Ambient air temperature for operation | 0-40 °C |
| Standards | ISO 9001, ISO 14001, SEMI F47, IEC 62477-1 |
| Height | 2152 mm |
| Product certifications | C-Tick, EAC, CE |