Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Noise measurement | 38...90 dBA |
| Mounting height | 1.2 m |
| Depth | 29 mm |
| Operating distance | 5...25 m |
| Noise measurement resolution | 0.01 dB |
| Temperature resolution | 0.1 °C |
| Width | 58 mm |
| Communication port protocol | IEEE 802.15.4 (LR-WPAN) 2.4 GHz |
| Type of measurement | ambient noise, relative humidity, temperature, volatile organic compounds (VOC), carbon dioxide (CO2) |
| Humidity measurement accuracy | +/- 5 % 20...80 % RH |
| VOC measurement accuracy | +/- (25 ppb + 10 % reading) |
| VOC measurement resolution | 1 ppb |
| Measurement temperature | 5-50 °C |
| Fixing mode | double-sided adhesive tape |
| Standards | ETSI EN 300 328:v2.1.1, AS/NZS 4268:2017, ISO/IEC 17067:2013, EN 62479:2010, EN 301-489-17:v3.2.0, EN 301-489-1:v2.2.0, EN 300-328:v2.1.1, EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, RSS GEN issue 4, FCC CFR 47 part 15:2016, RSS 247 issue 2, ANSI C63.10:2013 |
| Relative humidity | 20-80 % RH, non-condensing |
| Humidity measurement range | 20...80 % RH |
| Encryption protocol | automatic security key management using ECC + AES encryption |
| CO2 measurement repeatability | +/- (50 ppm + 5 % reading) |
| Temperature measurement accuracy | +/- 0.5 °C |
| Ambient air temperature for storage | 0-50 °C |
| VOC measurement range | 125...600 ppb |
| Height | 96 mm |
| Ambient air temperature for operation | 5-50 °C |
| Noise measurement accuracy | +/- 4 dB (80 Hz...6 kHz) |
| [Us] rated supply voltage | 5 V DC |
| Communication network type | IPv6 sensor network supporting mesh technology |
| Product certifications | RCM, IMDA Standards DA107248 |