| Attribute name | Attribute value |
|---|---|
| Main | |
| Analogue input type | thermocouple - 50...1768 °C with thermocouple S, thermocouple - 270...1372 °C with thermocouple K, thermocouple - 270...1300 °C with thermocouple N, thermocouple - 210...1200 °C with thermocouple J |
| Analogue input number | 2 |
| Analogue input resolution | 16 bits |
| Product or component type | analog input module |
| Range of product | Modicon TM5 |
| Complementary | |
| Input filtering | 1...66.7 ms configurable by software |
| Measurement resolution | 0.1 °C |
| Product compatibility | motion controller, logic controller |
| Range compatibility | Modicon LMC058, Modicon M258 |
| Temperature coefficient | 0.01 %FS/°C, analogue input type: thermocouple |
| Local signalling | 2 LEDs green for input status, 1 LED red for power supply, 1 LED green for power supply |
| Isolation | 500 Vrms AC insulation between channel and bus, no insulation between channels |
| Colour | white |
| Maximum power dissipation in W | 0.73 W |
| Current consumption | 30 mA at 24 V DC input/output, 2 mA at 5 V DC bus |
| Type of cable | shielded cable |
| Net weight | 0.025 kg |
| Marking | CE |
| Supply | internal |
| Common mode rejection | > 70 dB |
| Non-linearity | +/- 0.001 %FS, analogue input type: thermocouple |
| Measurement error | +/- 0.17 % of full scale - 50...1768 °C thermocouple S at 25 °C, +/- 0.11 % of full scale - 270...1372 °C thermocouple K at 25 °C, +/- 0.11 % of full scale - 270...1300 °C thermocouple N at 25 °C, +/- 0.1 % of full scale - 210...1200 °C thermocouple J at 25 °C |
| [Us] rated supply voltage | 24 V DC -15...20 % |
| Environment | |
| Operating altitude | 0...2000 m |
| Resistance to fast transients | 2 kV (power lines) conforming to IEC 61000-4-4, 1 kV (shielded cable) conforming to IEC 61000-4-4, 1 kV (I/O) conforming to IEC 61000-4-4 |
| Resistance to electrostatic discharge | 8 kV in air conforming to IEC 61000-4-2, 4 kV on contact conforming to IEC 61000-4-2 |
| Relative humidity | 5-95 % without condensation |
| Ambient air temperature for storage | -25-70 °C |
| Surge withstand | 1 kV common mode conforming to IEC 61000-4-5, 0.5 kV differential mode conforming to IEC 61000-4-5 |
| Pollution degree | 2 conforming to IEC 60664 |
| Electromagnetic compatibility | EN/IEC 61000-4-6 |
| Disturbance radiated/conducted | CISPR 11 |
| Shock resistance | 15 gn for 11 ms |
| Vibration resistance | 3.5 mm at 5-8.4 Hz on DIN rail, 1 gn at 8.4-150 Hz on DIN rail |
| IP degree of protection | IP20 conforming to IEC 61131-2 |
| Ambient air temperature for operation | 0-50 °C (vertical installation), 0-60 °C with derating factor (horizontal installation), 0-55 °C without derating (horizontal installation) |
| Storage altitude | 0-3000 m |
| Standards | IEC 61131-2, CSA C22.2 No 213, CSA C22.2 No 142, UL 508 |
| Resistance to electromagnetic fields | 10 V/m 80...2000 MHz conforming to IEC 61000-4-3, 1 V/m 2...2.7 GHz conforming to IEC 61000-4-3 |
| Product certifications | cULus, C-Tick, GOST-R, CSA |