Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Function of module | monitoring safety actuators for relay output |
| Device short name | XPSMCM |
| Electrical connection | screw terminal |
| [Us] rated supply voltage | 24 V - 20...20 % DC |
| Product or component type | safe relay output module |
| Number of outputs | 4 relay |
| Range of product | Preventa Safety automation |
| Complementary | |
| Safety level | SILCL 3 conforming to IEC 62061, can reach SIL 3 conforming to IEC 61508, can reach PL = e conforming to ISO 13849-1, can reach category 4 conforming to ISO 13849-1 |
| Depth | 114.5 mm |
| Width | 22.5 mm |
| Switching voltage | 10 V DC |
| Quantity per set | 1 |
| Mounting support | omega 35 mm DIN rail conforming to EN 50022 |
| Minimum switching current | 20 mA |
| Quality labels | CE |
| Maximum power dissipation in W | 3 W |
| Output type | relay, 4 NO + 2 NC circuit(s), volt-free |
| Maximum switching voltage | 250 V DC, 400 V AC |
| Net weight | 0.3 kg |
| Local signalling | 2 LEDs green/red with RELAY K1...K2 marking for relay contact, 2 LEDs orange with ADDR marking for node address, 1 LED red with E EX marking for external error, 1 LED red with E IN marking for internal error, 1 LED green with RUN marking for RUN (status), 1 LED green with PWR marking for power ON |
| Associated fuse rating | 3.5 A, slow-blow |
| Maximum switching current | 6 A |
| Cable cross section | 0.2-2.5 mm² - AWG 24...AWG 14 solid cablewithout cable end, 0.2-1 mm² - AWG 24...AWG 18 solid cablewithout cable end, 0.5-1.5 mm² - AWG 20...AWG 16 flexible cablewith cable end, with double bezel, 0.25-2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, without bezel, 0.25-2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, with bezel, 0.25-1 mm² - AWG 23...AWG 18 flexible cablewith cable end, without bezel, 0.2-2.5 mm² - AWG 24...AWG 14 flexible cablewithout cable end, 0.2-1.5 mm² - AWG 24...AWG 16 flexible cablewithout cable end |
| Integrated connection type | not connected to backplane expansion bus |
| Height | 99 mm |
| Number of terminal blocks | 6 |
| Switching time | 12 ms |
| Connections - terminals | 1 captive screw clamp terminals, removable terminal block, 2 captive screw clamp terminals, removable terminal block |
| Environment | |
| Insulation | 250 V AC between power supply and housing conforming to IEC 61800-5-1 |
| Electrical durability | 20000000 cycles |
| Overvoltage category | II |
| Safety reliability data | B10d = 10000000 utilisation category DC-13 24 V, , <2 A conforming to ISO 13849-1, B10d = 750000 utilisation category AC-15 230 V, , <1 A conforming to ISO 13849-1, B10d = 300000 utilisation category AC-15 230 V, , <3 A conforming to ISO 13849-1 |
| Mechanical durability | 20000000 cycles |
| Relative humidity | 10-95 % |
| Service life | 20 year(s) |
| Ambient air temperature for storage | -20-85 °C |
| IP degree of protection | IP20 |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 61800-5-1 |
| Shock resistance | 10 gn for 16 ms (1000 shocks on each axis) conforming to IEC 61496-1 |
| Vibration resistance | +/-0.35 mm (f= 10-55 Hz) conforming to IEC 61496-1 |
| Electromagnetic compatibility | susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3, susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 61000-4-3, electrostatic discharge immunity test - test level: 20 kV (on air) conforming to IEC 61000-4-2, electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to IEC 61000-4-2 |
| Pollution degree | 2 |
| Standards | IEC 61508, IEC 61800-5-1, ISO 13849-1, IEC 62061 |
| Ambient air temperature for operation | -10-55 °C |
| Product certifications | TÜV, cULus, RCM |