Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Electrical circuit type | addition to Preventa XPSU base module |
| Safety reliability data | type = B conforming to IEC 61508-1, SFF > 99% conforming to IEC 61508-1, PFHd = 1.61E-09 conforming to IEC 61508-1, HFT = 1 conforming to IEC 61508-1, SFF > 99% conforming to IEC 62061, PFHd = 1.61E-09 conforming to IEC 62061, HFT = 1 conforming to IEC 62061, PFHd = 1.61E-09 conforming to ISO 13849-1, Dcavg >= 99 % conforming to ISO 13849-1, MTTFd > 30 years conforming to ISO 13849-1 |
| Safety module application | for extending number of safety contacts |
| Safety module name | XPSUEP |
| Range of product | Harmony Safety Automation |
| [Us] rated supply voltage | 48...240 V AC/DC - 10...10 % |
| Safety level | can reach SIL 1 for normally closed relay contact conforming to IEC 61508, can reach SILCL 1 for normally closed relay contact conforming to IEC 62061, can reach PL c/category 1 for normally closed relay contact conforming to ISO 13849-1, can reach SIL 3 for normally open relay contact conforming to IEC 61508, can reach SILCL 3 for normally open relay contact conforming to IEC 62061, can reach PL e/category 4 for normally open relay contact conforming to ISO 13849-1 |
| Function of module | safety output extension |
| Connections - terminals | removable spring terminal block, 2 x 0.5...1.5 mm² flexible with ferrule with cable end, with bezel, removable spring terminal block, 2 x 0.25...1 mm² flexible with ferrule without cable end, with bezel, removable spring terminal block, 0.2...1.5 mm² solid or flexible twin conductor, removable spring terminal block, 0.25...2.5 mm² flexible with ferrule single conductor, removable spring terminal block, 0.2...2.5 mm² solid or flexible |
| Product or component type | safety module |
| Complementary | |
| Maximum response time on input open | 20 ms |
| Input protection type | internal, electronic |
| Maximum line resistance | 60 Ohm |
| Power consumption in W | 2 W 48 V DC |
| Auxiliary contact composition | 2 NC single, 4 NO redundant |
| [Ie] rated operational current | 3 A DC-13 for normally open relay contact, 5 A DC-1 for normally open relay contact, 3 A AC-15 for normally open relay contact, 5 A AC-1 for normally open relay contact |
| Power consumption in VA | 6.5 VA 240 V AC 50/60 Hz |
| Input compatibility | 3-wire proximity sensors PNP, OSSD pair conforming to IEC 61496-1-2, antivalent pair conforming to ISO 14119, normally closed circuit conforming to ISO 13850, mechanical contact conforming to ISO 14119, XC limit switch conforming to ISO 14119, normally closed circuit conforming to ISO 14119 |
| Number of inputs | 0 extension bus 24 V DC 5 |
| Associated fuse rating | 4 A gG for NC relay output circuit conforming to IEC 60947-1, 10 A gG for NO relay output circuit conforming to IEC 60947-1 |
| Minimum output voltage | 12 V for relay output |
| Height | 100 mm |
| Depth | 120 mm |
| Width | 22.5 mm |
| Local signalling | LED (yellow) for safety output status, LED (red) for error, LED (green) for power ON |
| [Ui] rated insulation voltage | 250 V (pollution degree 2) conforming to IEC 60947-1 |
| Net weight | 0.200 kg |
| [Uimp] rated impulse withstand voltage | 4 kV overvoltage category II conforming to IEC 60947-1 |
| [Ith] conventional free air thermal current | 8 A |
| Minimum output current | 10 mA for relay output |
| Mounting support | 35 mm symmetrical DIN rail |
| Environment | |
| Relative humidity | 5-95 % non-condensing |
| Ambient air temperature for storage | -25-85 °C |
| IP degree of protection | IP54 (mounting area) conforming to IEC 60529, IP40 (housing) conforming to IEC 60529, IP20 (terminals) conforming to IEC 60529 |
| Standards | IEC 62061 functional safety standard, ISO 13849-1 functional safety standard, IEC 61508-7 functional safety standard, IEC 61508-6 functional safety standard, IEC 61508-5 functional safety standard, IEC 61508-4 functional safety standard, IEC 61508-3 functional safety standard, IEC 61508-2 functional safety standard, IEC 61508-1 functional safety standard, IEC 60947-5-1 |
| Product certifications | cULus, TÜV |