Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Network type | AC |
| Device short name | iETL iTL 16 |
| Range | Acti9 |
| Range of product | iTL |
| Poles description | 2P |
| Pole contact composition | 1 C/O + 1 NO |
| Product or component type | extension for impulse relay |
| Relay application | remote control |
| [In] rated current | 16 A |
| Complementary | |
| Compatibility code | iETL iTL 16 |
| Electrical durability | AC-22: 100000 cycles, AC-21: 200000 cycles |
| Control signal type | impulse |
| Connections - terminals | tunnel type terminals - <= 6 mm² |
| Switching frequency | 5 switching operations/minute |
| Height | 60 mm |
| Market segment | residential, small commercial |
| 9 mm pitches | 2 |
| Range compatibility | Acti 9 Acti9 iTL iTLi, Acti 9 Acti9 iTL iTL |
| Product compatibility | iTL 16A |
| Colour | white |
| Mounting mode | fixed, on right side of TL |
| Impulse duration | 50 ms |
| Control type | remote control, toggle |
| Supply inrush power | 19 VA |
| Auxiliary connection terminal | tunnel type terminalscontrol circuit in 0.5-6 mm² |
| Remote control type | illuminated push-button 3 mA |
| [Ue] rated operational voltage | 415 V AC 50/60 Hz |
| Depth | 84 mm |
| Width | 18 mm |
| Local signalling | ON/OFF indication |
| Mounting support | 35 mm symmetrical DIN rail |
| [Uc] control circuit voltage | 6 V DC, 12 V AC 50/60 Hz |
| Network frequency | 50/60 Hz |
| Environment | |
| Relative humidity | 95-95 % at 55-55 °C |
| Ambient air temperature for storage | -40-70 °C |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Quality labels | KEMA, NF, CEBEC, VDE, IMQ |
| Product certifications | GOST |
| Pollution degree | 3 |
| Noise level | 60 dB |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20-50 °C |
| Standards | EN 669-1, EN 669-2-2 |