Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Device application | distribution |
| Range | Acti9 |
| Product or component type | pan assembly |
| Complementary | |
| Protection device type | miniature circuit breaker (MCB) 63 A max , residual current circuit breaker with overcurrent protection (RCBO) 45 A max |
| Depth | 90 mm |
| Width | 210 mm |
| Incomer device | 3P MCCB, 3P terminal block, 3P switch disconnector |
| [In] rated current | 250 A |
| Provided equipment | mounting plate |
| Rated voltage | 415 V AC 50/60 Hz |
| Number of poles | 24 x 18 mm |
| Short-circuit withstand | 25 kA 0.1 s |
| Length | 290 mm |
| [Ui] rated insulation voltage | 500 V |
| Range compatibility | Acti9 Acti9 Isobar B distribution board |
| Number of ways | 1 way (incomer) - 3P + N, 8 ways (outgoer) |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Busbar pitch | 18 mm |
| [Icw] rated short-time withstand current | 25 kA |
| Environment | |
| Standards | IEC 61439 |