Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Range of product | Zelio Logic |
| Product or component type | compact smart relay |
| Complementary | |
| Discrete input number | 12 |
| Operating rate in Hz | 10 Hz (no load) for relay output, 0.1 Hz (at Ie) for relay output |
| Isolation voltage | 1780 V |
| Tightening torque | 0.5 N.m |
| Supply voltage limits | 85-264 V |
| Electrical durability | DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to IEC 60947-5-1, DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to IEC 60947-5-1, AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to IEC 60947-5-1, AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to IEC 60947-5-1 |
| Local display | without |
| Discrete input frequency | 47...53 Hz, 57...63 Hz |
| [Us] rated supply voltage | 100...240 V AC |
| Checks | program memory on each power up |
| Switching capacity in mA | >= 10 mA at 12 V (relay output) |
| Mechanical durability | 10000000 cycles for relay output |
| Voltage state 1 guaranteed | >= 79 V for discrete input |
| Connections - terminals | screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end, screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid, screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end, screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid, screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid |
| Analogue input number | 0 |
| Net weight | 0.35 kg |
| Current state 1 guaranteed | >= 0.17 mA (discrete input) |
| Discrete input current | 0.6 mA |
| Number or control scheme lines | 0-500 with FBD programming, 0-240 with ladder programming |
| Supply frequency | 50/60 Hz |
| Protection type | against inversion of terminals (control instructions not executed) |
| Current state 0 guaranteed | <= 0.5 mA (discrete input) |
| Voltage state 0 guaranteed | <= 40 V for discrete input |
| Clock | with |
| Backup time | 10 years at 25 °C |
| Discrete input voltage | 100...240 V AC |
| Output thermal current | 8 A for all 8 outputs for relay output |
| Contacts type and composition | NO for relay output |
| Cycle time | 6-90 ms |
| Maximum supply current | 50 mA at 240 V (without extension), 100 mA at 100 V (without extension) |
| Overvoltage category | III conforming to IEC 60664-1 |
| Output voltage limits | 24...250 V AC, 5...30 V DC (relay output) |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1 |
| Response time | 5 ms (from state 1 to state 0) for relay output, 10 ms (from state 0 to state 1) for relay output, 50...255 ms with FBD programming (from state 1 to state 0) for discrete input, 50...255 ms with FBD programming (from state 0 to state 1) for discrete input, 50 ms with ladder programming (from state 1 to state 0) for discrete input, 50 ms with ladder programming (from state 0 to state 1) for discrete input |
| Power consumption in VA | 11 VA without extension |
| Clock drift | 6 s/month at 25-25 °C, 12 min/year at 0-55 °C |
| Number of outputs | 8 relay |
| Input impedance | 350 kOhm for discrete input |
| Environment | |
| Ambient air temperature for storage | -40-70 °C |
| Ambient air temperature for operation | -20-55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2, -20-40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2 |
| Disturbance radiated/conducted | class B conforming to EN 55022-11 group 1 |
| Operating altitude | 2000 m |
| Maximum altitude transport | 3048 m |
| Immunity to microbreaks | 10 ms |
| Product certifications | C-Tick, UL, CSA, GOST, GL |
| Relative humidity | 95-95 % without condensation or dripping water |
| Pollution degree | 2 conforming to IEC 61131-2 |
| IP degree of protection | IP40 (front panel) conforming to IEC 60529, IP20 (terminal block) conforming to IEC 60529 |
| Environmental characteristic | low voltage directive conforming to IEC 61131-2, EMC directive conforming to IEC 61131-2 zone B, EMC directive conforming to IEC 61000-6-4, EMC directive conforming to IEC 61000-6-3, EMC directive conforming to IEC 61000-6-2 |
| Standards | IEC 61000-4-6 level 3, IEC 60068-2-27 Ea, IEC 61000-4-5, IEC 61000-4-4 level 3, IEC 61000-4-12, IEC 61000-4-2 level 3, IEC 60068-2-6 Fc, IEC 61000-4-11, IEC 61000-4-3 |