| Attribute name | Attribute value |
|---|---|
| Main | |
| Analogue input resolution | 10 bits |
| Type of filter | single low pass input filter 25 Hz |
| Range of product | Modicon STB distributed I/O solution |
| Analogue input type | voltage 0...10 V |
| Kit composition | STBXBA1000 base, STBXTS1100, 6-terminal screw type connector, STBXTS2100, 6-terminal spring clamp connector, STBAVI1255 module |
| Analogue input number | 2 |
| Product or component type | basic analog input kit |
| Complementary | |
| Product compatibility | power distribution module STBPDT3100/3105, mounting base STBXBA1000 |
| Update time | 10 ms |
| Addressing requirement | 2 input words |
| Temperature drift | +/-0.01 %/°C |
| Marking | CE |
| Data format | IEC 61131-2, EN 61131-2 |
| Hot swapping fallback | no for basic NIMs |
| Status LED | 1 LED (green) module status (RDY) |
| Insulation between channels and sensor bus | 30 V |
| Cold swapping | yes |
| Insulation between channels and logic bus | 1500 V for 1 minute |
| [Us] rated supply voltage | 24 V DC |
| Overvoltage category | II |
| Maximum source impedance | 1 kOhm |
| Absolute maximum input | 50 V DC |
| Response time | 5 ms |
| Absolute accuracy error | +/- 0.5 % of full scale 25 °C |
| Net weight | 0.116 kg |
| Current consumption | 30 mA at 5 V DC for logic bus |
| Supply | power distribution module |
| Integral linearity | +/- 0.2 %FS |
| Differential linearity | monotonic |
| Input impedance | 400 kOhm |
| Maximum supply current for sensors | 100 mA per input channels |
| Environment | |
| Ambient air temperature for operation | 32...140 °F without derating, 0-60 °C |
| Relative humidity | 95-95 % at 60-60 °C without condensation |
| Ambient air temperature for storage | -40-85 °C without derating, -40...185 °F without derating |
| Pollution degree | 2 conforming to IEC 60664-1 |
| IP degree of protection | IP20 conforming to IEC 61131-2 class 1 |
| Operating altitude | <= 2000 m |
| Vibration resistance | 5 gn at 58-150 Hz on 35 x 15 mm symmetrical DIN rail, 3 gn at 58-150 Hz on 35 x 7.5 mm symmetrical DIN rail, +/-0.35 mm at 10-58 Hz |
| Shock resistance | 30 gn for 11 ms conforming to IEC 88 reference 2-27 |
| Product certifications | C-Tick, CSA, UL, ATEX Cat 3G, FM Class 1 Division 2 |