| Attribute name | Attribute value |
|---|---|
| Main | |
| Number of protected poles | 4 |
| Trip unit technology | thermal-magnetic |
| Network type | AC/DC |
| Device short name | iC60H |
| Breaking capacity | 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2, 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2, 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2, 42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2, 10000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1, 15 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2 |
| Range | Acti9 |
| Curve code | D |
| Range of product | Acti9 |
| Poles description | 4P |
| Utilisation category | category A conforming to EN/IEC 60947-2 |
| Product name | Disbo iC60 |
| Product or component type | miniature circuit-breaker |
| Breaking capacity code | H |
| [In] rated current | 63 A |
| Complementary | |
| Provision for padlocking | padlockable |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
| Compatibility code | iC60 |
| Electrical durability | 10000 cycles |
| Connections - terminals | single terminal (top or bottom) 1-25 mm² flexible, single terminal (top or bottom) 1-35 mm² rigid |
| Earth-leakage protection | separate block |
| Height | 85 mm |
| [Ics] rated service breaking capacity | 10 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V DC, 7500 A 75 % conforming to EN/IEC 60898-1 - 415 V AC 50/60 Hz, 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz, 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz, 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz, 21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Net weight | 0.5 kg |
| Magnetic tripping limit | 12 x In +/- 20 % |
| 9 mm pitches | 8 |
| Tightening torque | 3.5-3.5 N.m top or bottom |
| Colour | white |
| Connection pitch | 18 mm between phases |
| Mechanical durability | 20000 cycles |
| Power losses per pole | 5.6 W |
| Mounting mode | clip-on |
| Control type | toggle |
| Wire stripping length | 14 mm for top or bottom connection |
| Depth | 78.5 mm |
| Width | 72 mm |
| Local signalling | trip indicator |
| Limitation class | 3 conforming to EN/IEC 60947-2 |
| Mounting support | rail |
| Contact position indicator | yes |
| Total power losses | 16.8 W |
| Network frequency | 50/60 Hz |
| Environment | |
| Relative humidity | 95-95 % at 55-55 °C |
| Ambient air temperature for storage | -40-85 °C |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Pollution degree | 3 conforming to EN/IEC 60947-2 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -35-70 °C |