| Attribute name | Attribute value |
|---|---|
| Main | |
| [Ie] rated operational current | 275 A (at <40 °C) at <= 1000 V AC-1, 150 A (at <60 °C) at <= 440 V AC-3 |
| Utilisation category | DC-5, DC-3, DC-1, AC-6b, AC-6a, AC-5b, AC-5a, AC-1, AC-3e, AC-3 |
| [Uc] control circuit voltage | 200...500 V DC, 200...500 V AC 50/60 Hz |
| Device short name | LC1G |
| Range | TeSys |
| Control circuit voltage limits | drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C), operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) |
| Range of product | TeSys Giga |
| Poles description | 4P |
| Product or component type | contactor |
| Contactor application | power switching |
| [Ue] rated operational voltage | <= 460 V DC, <= 1000 V AC 50/60 Hz |
| Complementary | |
| Compatibility code | LC1G |
| Electrical durability | 300 cycles AC-1 at Ue 400 V |
| Number of modules per PLC per PC | 1 |
| Associated fuse rating | 315 A gG at <= 690 V, 160 A aM at <= 690 V for motor, 160 A aM at <= 440 V for motor |
| Height | 255 mm |
| Inrush power in W | 215 W |
| [Ui] rated insulation voltage | 1000 V |
| Overvoltage category | III |
| Mechanical durability | 8 Mcycles |
| Coil technology | built-in bidirectional peak limiting |
| Inrush power in VA | 295-295 VA |
| Net weight | 5.1 kg |
| Auxiliary contact composition | 1 NO + 1 NC |
| Average impedance | 0.00018 Ohm |
| Power dissipation per pole | 5 W AC-3 - Ith 150 A, 10 W AC-1 - Ith 275 A |
| Product certifications | EU-RO-MR by DNV-GL, UKCA, CE, EAC, cULus, CCC, CB Scheme |
| [Icw] rated short-time withstand current | 0.35 kA - 10 min, 0.45 kA - 3 min, 0.6 kA - 1 min, 0.7 kA - 30 s, 1.2 kA - 10 s |
| Tightening torque | 18 N.m |
| Operating time | 15...50 ms opening, 40...70 ms closing |
| Irms rated making capacity | 1890 A at 440 V |
| Rated breaking capacity | 1280 A at 440 V |
| [Ith] conventional free air thermal current | 275 A (at 40 °C) |
| Connection pitch | 35 mm |
| Depth | 193 mm |
| Width | 143 mm |
| Hold-in power consumption in VA | 13.0-13.0 VA |
| Maximum operating rate | 300 cyc/h AC-1, 600 cyc/h AC-3e, 600 cyc/h AC-3 |
| Connections - terminals | control circuit: push-in 0.75-2.5 mm² - cable stiffness: flexible with cable end, control circuit: push-in 0.75-2.5 mm² - cable stiffness: solid stranded without cable end, control circuit: push-in 2 0.5-1.0 mm² with cable end, control circuit: push-in 1 0.25-2.5 mm² - cable stiffness: flexible with cable end, control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end, power circuit: bolted connection, power circuit: lugs-ring terminals 1 185-185 mm², power circuit: bar 2 - busbar cross section: 25 x 6 mm |
| Pole contact composition | 4 NO |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Hold-in power consumption in W | 8.0-8.0 W |
| Mounting support | plate |
| Standards | JIS C8201-5-1, JIS C8201-4-1, CSA C22.2 No 60947-4-1, UL 60947-4-1, EN/IEC 60947-5-1, EN/IEC 60947-4-1 |
| Environment | |
| Mechanical robustness | shocks 15 gn 11 ms contactor closed, shocks 10 gn 11 ms contactor open, vibrations 5-300 Hz 4 gn contactor closed, vibrations 5-300 Hz 2 gn contactor open |
| Ambient air temperature for storage | -60-80 °C |
| Permissible ambient air temperature around the device | -40-70 °C at Uc |
| Colour | dark grey |
| IP degree of protection | IP2X front face with shrouds conforming to VDE 0106, IP2X front face with shrouds conforming to IEC 60529 |
| Protective treatment | TH |
| Ambient air temperature for operation | -25-60 °C |