Don't have an account?
| Attribute name | Attribute value |
|---|---|
| Main | |
| Device short name | PM8243 |
| Range | PowerLogic |
| Market segment | utility: sub feeder, industry network management: sub feeder, industry network management: main incomer, healthcare network management: sub feeder, healthcare network management: main incomer, data center network management: sub feeder, data center network management: main incomer, buildings multi-site network management: sub feeder, buildings multi-site network management: main incomer, buildings large building network management: sub feeder, buildings large building network management: main incomer, buildings medium building network management: main incomer, buildings small building network management: main incomer, buildings large building cost management: billing: sub feeder |
| Product name | PowerLogic PM8000 |
| Product or component type | power meter |
| Complementary | |
| Device application | power monitoring, WAGES metering |
| Display type | without display |
| Web services | HTTPS server, viewing of captured waveform (web), viewing of captured waveform (FTP), alarm notification by e-mail, web server, file upload/download via SFTP, file upload/download via FTP, customizable home page |
| Measurement accuracy | active energy +/- 0.2 %, voltage +/- 0.1 %, current +/- 0.1 % |
| Mounting mode | clip-on |
| [Us] rated supply voltage | 110...415 V DC +/- 10 %, 90...415 V AC 45...65 Hz +/- 10 % |
| Information displayed | harmonic distortion, energy consumption, power, frequency, current, voltage |
| Depth | 90.8 mm |
| Frequency measurement range | 42-69 Hz |
| Communication service | PTP time synchronization, NTP time synchronization, RSTP support, DHCP, SMTP e-mail notification |
| Communication port protocol | RSTP 801.1d 2004, Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s, Modbus TCP/IP, IEC 61850, DNP3, ION at 115 kbauds - 2-wire, Modbus RTU at 115 kbauds - 2-wire |
| Type of measurement | power factor per phase, rms, apparent power per phase, rms, active and reactive power per phase, rms, power factor total, apparent power total, active and reactive power total, frequency, voltage, current |
| Product certifications | N998, cULus, CE |
| Memory capacity | 512 MB |
| Height | 90.5 mm |
| Power quality analysis | rapid voltage change, disturbance direction detection, conforming to IEC 62586 power quality monitoring, programmablity (logic and math functions), voltage sag and swell detection, waveform capture, harmonic distortion, up to the 63rd harmonic, conforming to IEC 61000-4-30: class S power quality measurement, conforming to IEEE 519: 2014 compliance report, conforming to EN 50160: 2010 compliance report |
| Communication port support | screw terminal block: RS485, ETHERNET |
| Installation category | III |
| Accuracy class | class 0.2 current conforming to IEC 61557-12, class 0.2 voltage conforming to IEC 61557-12, class 0.5 power factor conforming to IEC 61557-12, class 0.5S reactive energy conforming to IEC 62053-24, class 0.2 active power conforming to IEC 61557-12, class 0.2 active energy conforming to ANSI C12.20, class 0.2S active energy conforming to IEC 62053-22 |
| Width | 90.5 mm |
| Analogue input type | current (impedance 0.3 mOhm), voltage (impedance 5 MOhm) |
| Isolation voltage | III347-600 V conforming to CSA C22.2 No 61010-1:ed. 3, III347-600 V conforming to UL 61010-1:ed. 3, III400-690 V conforming to EN 61010-1:ed. 3, III400-690 V conforming to IEC 61010-1:ed. 3 |
| Cybersecurity | Syslog protocol support, robust security logs, enable/disable communication ports, port hardening, password protection |
| [In] rated current | 5 A, 10 A, 1 A |
| Data recording | 50 data recorders, event logs, min/max of instantaneous values, sequence of event recording, alarm logs, waveform logs, trending/forecasting, data logs, time stamping, GPS synchronisation, sag and swell logs, harmonics logs |
| Poles description | 3P, 3P + N, 1P + N |
| Mounting support | DIN rail |
| Measurement current | 50-10000 mA |
| Net weight | 528 g |
| Number of inputs | 3 digital 60 V DC, 3 digital 30 V AC |
| Power consumption in VA | 18 VA at 415 V AC |
| Number of outputs | 1 pulse |
| Standards | IEC 61326-1, IEC 62586-2, IEEE 1588, IEC 62053-24, IEC 62053-22, IEC 62052-11, IEC 61557-12 |
| Sampling rate | 256 samples/cycle |
| Measurement voltage | 100-690 V AC 42...69 Hz between phases, 57-400 V AC 42...69 Hz between phase and neutral |
| Network frequency | 60 Hz, 50 Hz |
| Communication network type | IPv6 (internet protocol) |
| Environment | |
| Compatibility code | PM8243 |
| IP degree of protection | IP30 conforming to IEC 60529 |
| Relative humidity | 5-95 % |
| Ambient air temperature for storage | -40-85 °C |
| Electromagnetic compatibility | surge withstand conforming to IEEE C37.90.1, conducted RF disturbances (2...150 Hz) conforming to CLC/TR 50579, conducted and radiated emissions conforming to ICES-003, conducted and radiated emissions conforming to FCC part 15, conducted and radiated emissions conforming to EN 55011, conducted and radiated emissions conforming to EN 55022, immunity to impulse waves conforming to IEC 61000-4-12, voltage dips and interruptions immunity test conforming to IEC 61000-4-11, magnetic field at power frequency conforming to IEC 61000-4-8, conducted RF disturbances conforming to IEC 61000-4-6, surge immunity test conforming to IEC 61000-4-5, electrical fast transient/burst immunity test conforming to IEC 61000-4-4, radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3, electrostatic discharge conforming to IEC 61000-4-2 |
| Ambient air temperature for operation | -25-70 °C |
| Operating altitude | 3000 m |